$3,450AUD

Solid State Motor Starter Zener Smartstart 480

Offered by: Shane

Description

Zener Smartstart 480 solid-state motor starter

This Item is in new condition never been used comes in box with manual.

See Below for Specs:

P/N TC21750
S/N 2634/06

Input supply : 208-480V AC : 3 PHASE
Output Current: Motor F.L.C.
3 Wire: 195A Med : 135A Heavy
6 Wire: 315A Med : 215A Heavy
Control Supply: 110/230V AC


ELECTRICAL
Motor Supply: 208-480 V AC (+10%,-10%)
Frequency: 50/60Hz (automatic adjustment)
Power Circuit Fusing: Ultra-fast semiconductor fuses included as standard
Equipment Grounding: Earth stud provided on top of chassis
PIV Rating: 1400 V DC minimum
dv/dt suppression: RC snubber network
Motor Configuration: 3 wire or 6 wire connected
Control Supply: 110/220 – 240 V AC (+10%,-10%)
Start/Stop Supply: 110/220 – 240 V AC (+10%,-10%)
Start/Stop: 110 – 240 V AC two or three wire control
Power Consumption: 60 VA maximum for control circuitry
Control Circuit Fuse: 2A HRC fuse (customer supplied)
ENVIRONMENTAL
Operating Temperature: 0°C to 55°C (derate 1% per °C above 45°C)
Humidity: 0% to 95% non condensing
Altitude: 1000m ASL Maximum
Airborne Matter: Suitable for non conducting and non flammable dusts only
Storage: Clean dry location -20°to 60°C
Protection Bag: IP00
FUNCTIONAL
Ramp Control: 1, 2, 5, 10, 20, 30, 45, 60 seconds
Ramp Type: Linear increase in SCR conduction angle
Extended Stop Control: 0.5, 1, 2, 4 times selected acceleration time
Pump Stop Control: (Optional) adjustable deceleration profile to minimise water hammer
Current Limit Control: 200, 225, 250, 275, 300, 325, 350, 375, 400, 450% of nominal FLC
Pulse Start: 0.5, 1.0, 2.0, s of near full voltage for starting positive displacement
pumps and loads that stick firm at rest
Status Indication: Power On, Standby, Accelerating, Up to Speed, Bypass Mode,
Decelerating, Energy Save, 3 Wire Mode
Fault Indication: Fault, Control Voltage, Bypass Fault, Overtemperature, Phase
Reversal, Motor Stalled, Phase A,B,C
Relay Output: Healthy run condition is signalled by a set of change over contacts
Bypass Conductor Signal: Normally open contact closes for bypass
Relay Contact Rating: 5A @250 V AC or 5A @ 30V DC resistive, @A @ 250V AC inductive
Maximum Duty Cycle: FLC continuously
Medium Duty Cycle: 300% FLC 30 seconds
200% FLC 60 seconds
Heavy Duty Start: 450% FLC 30 seconds
300% FLC 60 seconds
PROTECTION
Phase Loss: Loss of phase upstream or downstream controller
SCR Fault: Detection of short circuit, open circuit or firing faults on SCRs
Motor Stall: Detection of stalled or underspeed motor condition
Auto Restart: Unit will restart on fault trip condition for 3 consecutive attempts
Overtemperature: Thermal sensor controls cooling fans and overtemperature trip
Short Circuit: Ultra-fast semiconductor fuses included as standard
This item was listed more than six months ago and may no longer be available, contact details are no longer available. Ad still shown to give releated ads only.